When a DG (diesel
generator) is connected to PuREPower, it has to do two jobs at the same time:
run your loads and charge the PuREPower battery. So the DG must be bigger than
the PuREPower rating. In this blog, DG sizes are given for both single-phase
and three-phase DG sets.
Simple rule:
● Three-phase models (15.0 Lite,
20.0, 30.0, 60.0, 120.0): DG = 1.5 × PuREPower rating,
rounded up to the next standard DG size. The extra 50% covers the battery
charging that runs together with your loads.
● Single-phase models (3.0
Lite, 3.0, 5.0, 12.0): use a single-phase DG = 1.5 ×
PuREPower rating, or a three-phase DG = 1.5 × PuREPower rating × 3. Both are
rounded up to the next standard DG size. A three-phase DG must be 3 times
bigger, because each phase gives only one third of its rating.
|
PuREPower
model |
PuREPower phase |
PuREPower rating |
Single-phase DG |
Three-phase DG |
|
3.0
Lite and 3.0 |
Single
phase |
3.0
kW |
5
kVA (1.5 × 3.0 = 4.5) |
15
kVA (1.5 × 3.0 × 3 = 13.5) |
|
5.0 |
Single
phase |
5.0
kW |
10
kVA (1.5 × 6.2 = 9.3) |
30
kVA (1.5 × 6.2 × 3 = 27.9) |
|
12.0 |
Single
phase |
12.0
kW |
20
kVA (1.5 × 12 = 18) |
62.5
kVA (1.5 × 12 × 3 = 54) |
|
15.0
Lite |
Three
phase |
15.0
kW |
Not
applicable |
25
kVA (1.5 × 15 = 22.5) |
|
20.0 |
Three
phase |
20.0
kW |
Not
applicable |
30
kVA (1.5 × 20 = 30) |
|
30.0 |
Three
phase |
30.0
kW |
Not
applicable |
45
kVA (1.5 × 30 = 45) |
|
60.0 |
Three
phase |
60.0
kW |
Not
applicable |
100
kVA (1.5 × 60 = 90) |
|
120.0 |
Three
phase |
120.0
kW |
Not
applicable |
180
kVA (1.5 × 120 = 180) |
The working behind each number is in the sections below. DG sizes are rounded up to the next common Indian DG rating.

Three-phase
models: DG (kVA) = 1.5 × PuREPower rating (kW)
Single-phase
models, single-phase DG: DG (kVA) = 1.5 × PuREPower rating (kW)
Single-phase
models, three-phase DG: DG (kVA) = 1.5 × PuREPower rating (kW) × 3
Worked example: PuREPower 5.0
● PuREPower rating: 6.2 kW
● 1.5 × 6.2 = 9.3 kVA
● Single-phase DG: round up to 10
kVA
● Three-phase DG: 9.3 × 3 = 27.9
kVA, round up to 30 kVA
Things to know:
Example:
20 kVA three-phase DG with PuREPower 12.0
A three-phase DG has three separate outputs, called phases (R, Y, and B). Its total rating is shared equally between these three phases.
PuREPower 12.0 is a single-phase product, so it is connected to only one phase
and the neutral of the DG. It can use only the power available on that one phase.
● DG rating: 20 kVA, three phase
● Power available on each phase: 20 ÷ 3 = about 6.7 kVA
● PuREPower 12.0 needs 1.5 × 12 = 18 kVA on that one phase
● Result: the phase in use is overloaded about 3 times, while the other two phases
stay unused.
What
the customer will see:
● The DG voltage drops and the
frequency dips when loads and battery charging start.
● PuREPower rejects the DG and goes
back to the battery, then reconnects again and again.
● The DG gets hot and may trip on
overload. Running a DG this unbalanced can damage its alternator over time.
The
right choice:
● Use a 20 kVA single-phase DG (1.5
× 12 = 18 kVA, rounded up) or a 62.5 kVA three-phase DG (1.5 × 12 × 3 = 54
kVA, rounded up). Each phase of the 62.5 kVA DG gives about 21 kVA.
● The same applies to PuREPower 3.0
and 5.0: use a 5 kVA single-phase DG or a 15 kVA three-phase DG for 3.0, and a
10 kVA single-phase DG or a 30 kVA three-phase DG for 5.0.
PuREPower will only
accept (synchronise with) a DG whose output looks like clean grid power. Check
these before commissioning:
|
Check |
What PuREPower needs |
Why it matters |
|
Voltage |
170–280
V phase to neutral (3.0 Lite 3.0, 5.0, 12.0); 155–483 V three phase (20.0,
30.0); 380–440 V three phase (15.0 Lite, 60.0, 120.0) |
Outside
this window, PuREPower rejects the DG and stays on battery. |
|
Frequency |
Steady
50 Hz (or 60 Hz) |
PuREPower
must lock onto the DG waveform before it transfers the loads. |
|
AVR |
DG
fitted with an automatic voltage regulator |
Holds
voltage steady when charging and loads switch on. |
|
Governor |
Electronic
or good mechanical governor |
Keeps
frequency steady; a hunting DG keeps dropping in and out. |
|
Waveform |
Low
distortion, no heavy ripple |
"Ripple
too high" protection disconnects a poor DG. |
|
Rating
basis |
DG
rated in kVA at 0.8 pf |
Always
compare in kVA, not kW. |
|
Derating |
Reduce
the DG rating for high altitude or temperature, as per the DG maker. |
A
derated DG gives less than its nameplate. |
|
Auto
start |
DG
with a two-wire remote start (dry contact) |
PuREPower
can start the DG from its dry-contact pins 7 (DO+) and 8 (DO−) |
How to let PuREPower start the DG by itself:
Everything you need to know about this topic.